Chiller sizing when you know inlet water temperatures leaving chill water temperature required and flow rate.

1. Calculate Temperature Differential (rT°F)
rT°F = Inlet Water Temperature (°F) -Leaving Chill Water Temperature

2. Calculate BTU/hr.
BTU/hr. = Gallons per hr x 8.33 x rT°F

3.
Calculate tons of cooling capacity
Tons = BTU/hr. ÷ 12,000


4.
Over Size Chiller by 20%


Example : What size chiller is required to cool 40GPM from 70°F to 58°F

1.
rT°F = 70°F - 58°F = 12°F

2.
BTU/hr. = 40gpm x 60 x 8.33 x 12°F = 239,904 BTU/hr.

3.
Ton Capacity = 239,904 BTU/hr. ÷ 12,000 = 19.992 Tons

4.
Calculate BTU/hr.
BTU/hr. = Gallons per hr x 8.33 x rT°F

Solution:
Required Size = 19.992 x 1.2 = 23.9904 or 25-Ton