| Chiller
sizing when you know inlet water temperatures leaving chill water temperature
required and flow rate. 1.
Calculate Temperature Differential (rT°F)
rT°F = Inlet Water Temperature (°F) -Leaving Chill Water Temperature 2.
Calculate BTU/hr.
BTU/hr. = Gallons per hr x 8.33 x rT°F 3. Calculate tons of cooling capacity Tons = BTU/hr. ÷ 12,000
Example
: What size chiller is required to cool 40GPM from 70°F to
58°F
1. rT°F = 70°F - 58°F = 12°F 2. BTU/hr. = 40gpm x 60 x 8.33 x 12°F = 239,904 BTU/hr. 3. Ton Capacity = 239,904 BTU/hr. ÷ 12,000 = 19.992 Tons 4. Calculate BTU/hr. BTU/hr. = Gallons per hr x 8.33 x rT°F Solution: Required Size = 19.992 x 1.2 = 23.9904 or 25-Ton |
|||||||
|
COLD SHOT
CHILLERS™. |
|||||||